Basic specifications | |
Rated voltage | 3.3kV, 6kV, 10kV |
Rated capacity | ±800kvar~±6000kvar |
Rated frequency | 50Hz |
Main function | Compensate reactive power, improve power factor, suppress voltage flicker and improve power quality |
Performance index | |
Overload capacity | 110%/60min, 120%/1min |
Response time | ≤5ms |
Active power loss | ≤0.8% |
THDi | ≤3% |
Var compensation mode | Capacitive and inductive automatic continuous smooth adjustment |
Starting compensation power | 5kVar |
Compensation current resolution | 0.5A |
Running mode | Constant device reactive power mode Constant assessment point reactive power mode Constant assessment point power factor mode Constant assessment point voltage mode Load compensation mode |
Display and interface | |
Display | 7-inch HMI |
Communication port | RS485, High speed optical fiber |
Communication protocol | Standard MODBUS_RTU, optional Profibus, CDT91, IEC61850-103/104, CANOPEN, user define. |
Protection functions | |
Protection | Bus overvoltage, power unit overtemperature, system overload, system short circuit, system overvoltage, system frequency abnormality protection, external fault protection, system power supply abnormality and other protection functions. |
Others | |
Cooling mode | Heat pipe + forced air cooling |
IP degree | IP54,Ex d [ib] I Mb |
Dimension | Refer to the dimension list |
Environment | Higher than GB3836.1-2010 |
SVG Model No. | Rated Capacity (kvar) | Rated Voltage (kV) | Cooling mode | Weight(kg) | Dimension | ||
W | D | H | |||||
WJL1-800/3.3~ WJL1-2000/3.3 |
800~2000 | 3.3 | Water cooling | 7000 | 2100 | 1400 | 1500 |
WJL1-1000/6~ WJL1-2500/6 |
1000~2500 | 6 | 12000 | 3500 | 1500 | 1750 | |
WJL1-1000/10~ WJL1-6000/10 |
1000~6000 | 10 | 13000 | 4500 | 1400 | 1780 |